Differential Pressure Analog Sensor – HK Instruments

 

Accuracy (from applied pressure):
(models 250 and 2500)
Pressure < 125 Pa = 1 % + ±2 Pa
Pressure > 125 Pa = 1 % + ±1 Pa
Accuracy (from applied pressure):
(model 7000)
Pressure< 125 Pa = 1.5 % + ±2 Pa
Pressure > 125 Pa = 1.5 % + ±1 Pa
Zero point calibration: automatic with autozero element (-AZ) or by pushbutton
Measuring units: Pa, kPa, mbar, inchWC, mmWC, psi
Measuring element: MEMS, no flow-through
Supply voltage: 24 VDC ±10 % / 24 VAC ±10 %
Power consumption: < 1.0 W (< 1.2 W with output current 20 mA)
Output signals (3-wire): 0…10 VDC, Load R minimum 1 kΩ
4…20 mA, maximum load 500 Ω
Operating temperature: -20…+50 °C (with autozero calibration -5…+50 °C) -40…+50 °C (-40C model)
Response time: 0.8 / 8 s